消防控製室的安裝要考慮哪些?

來源:http://gzfscs.cn/ 日期(qi):2023-10-24

1.主消防控製室的消防設備能夠對
1. The fire protection equipment in the main fire control room can
係統內共用消防設備進行控製,顯示其狀態信息,並能夠顯示各個分消防控製室內消防設備的狀態信息,具備
The system shares fire equipment for control, displays its status information, and can display the status information of fire equipment in each sub fire control room
對消防控製室內消防設備及其所控製的消防係統、設備的控製功能。
The control function of the fire equipment in the fire control room and the fire system and equipment it controls.
2.各個分消防控製室的消防設備之間,可以互相傳輸、顯示狀態信息,不能互相控製消防設備。
2. The fire equipment in each sub fire control room can transmit and display status information to each other, but cannot control each other's fire equipment.
3.消防控製室內設置的消防設備應能監控並顯示建築消防設施運行狀態信息,並應具有向城市消防遠程監控中心傳輸信息的功能。
3. The fire equipment installed in the fire control room should be able to monitor and display the operational status information of building fire protection facilities, and should have the function of transmitting information to the urban fire remote monitoring center.
川消
4.消防控製室的供電,應在其配電線路的最末一級配電箱處設置自動切換裝置。
4. For the power supply of the fire control room, an automatic switching device should be installed at the last level distribution box of its distribution line.
5.消防控製室以及發生火災時仍需正常工作的消防設備房應設置備用照明,其作業麵的最低照度不應低於正
5. Backup lighting should be installed in the fire control room and the fire equipment room that still needs to work normally in the event of a fire, and the minimum illumination on the working surface should not be lower than positive
常照明的照度。
The illuminance of regular lighting.
6.設置火災自動報警係統和需要聯動控製的消防設備的建築(群)應設置消防控製室。
6. Buildings (clusters) with automatic fire alarm systems and fire equipment that require linkage control should be equipped with fire control rooms.
7.附設在建築內的消防控製室應采用耐火極限不低於2.00h的防火隔牆和1.50h的樓板與其他部位分隔。消防控製室開向建築內的門應采用乙級防火門。
7. The fire control room attached to the building should be separated from other parts by a fire partition wall with a fire resistance limit of no less than 2.00h and a 1.50h floor slab. The doors in the fire control room that open into the building should use Class B fire doors.
8.附設在汽車庫、修車庫內的消防控製室應采用防火隔牆和耐火極限不低於1.50h的不燃性樓板相互隔開或與相鄰部位分隔。
8. The fire control room attached to the garage and repair garage should be separated from each other or adjacent parts by fire partition walls and non combustible floor slabs with a fire resistance limit of not less than 1.50 hours.
本文由川消提供技術支持,更多的詳細精彩內容請點擊污黄美女APP下载的網站 http://gzfscs.cn ,污黄美女APP下载將會全心全意為您提供滿意的服務。
This article is provided by Chuanxiao with technical support. For more detailed and exciting content, please click on our website http://gzfscs.cn We will wholeheartedly provide you with satisfactory service.